FLUKE 40mm 300a 368 FC Leakage Current Clamp Meter FLU368FC
Quantity
-
Detail
The Fluke 368 true-rms leakage current clamp meter helps users detect, document, record and compare leakage current readings over time as a means of preventing unplanned downtime, and identifying intermittent GFCI and RCD trips, all without taking equipment off line.
The Fluke 368 has a large 40 mm diameter jaw for work with large conductors. The clamp’s jaw is fully shielded to accurately capture very small leakage signals, and to minimize external electromagnetic interference.
True-rms measurements for accuracy when measuring complex, non-sinusoidal waveforms
40 mm jaw opening
Highest resolution of 1 μA, measure up to 60 A
Selectable filter function removes unwanted noise
Max/Min/Average readings and hold function
Forward-facing LED worklight for use in dark wiring cabinets
Backlit display; auto backlight off and auto power off for extended battery life
CAT III 600V safety ratingSpecifications:
Electrical Specifications
- Measurement function: Alternating current
- AC ampere range: 3 mA, 30 mA, 300 mA, 3 A, 30 A, 60 A
- Range selection:
- mA / A: manual selection
- 3 mA / 30 mA / 300 mA: automatic selection
- 3 A / 30 A / 60 A: automatic selection
- Range / Resolution:
- 3 mA¹ / 0.001 mA
- 30 mA / 0.01 mA
- 300 mA / 0.1 mA
- 3 A / 0.001 A
- 30 A / 0.01 A
- 60 A / 0.1 A
- Accuracy – filter activated (40 to 70 Hz), filter off (40 to 1 kHz)²:
- 3 mA – 30 A = 1% + 5 digits
- 60 A = 2% + 5 digits
- Frequency: 40 Hz to 1 kHz
- Crest Factor: 3
After calibration accuracy is valid for one year. Accuracy is expressed as ± (% of reading + digits). Reference conditions 23 ±5 °C and a maximum relative humidity of 80%.
¹The minimum value is 10 μA rms.
²Outside of the TC / °C 18 °C to 28 °C, 0.02 + 1Physical
- Display (LCD): Digital readout: 3300 count
- Display refresh rate: 4 times / sec
- Maximum conductor diameter: 40 mm
- Dimensions: 234 x 101 x 46 mm
- Weight: 500 g
- Battery: 2 AA, IEC LR6, NEDA 15A, alkaline
- Battery life: Expected battery life, without using backlight and spotlight, is more than 150 hours
- Automatic shut-down: Meter automatically shuts down after 15 minutes of inactivity
Safety and Environmental Specifications
- General safety: IEC 61010-1: Pollution Degree 2
- Measurement safety: IEC 61010-2-032: CAT III 600 V / CAT IV 300 V
- Operating temperature: -10 °C to +50 °C
- Storage temperature: -40 °C to +60 °C
- Operating humidity:
- Non-condensing (<10 °C)
- 90% relative humidity (10 °C to 30 °C)
- 75% relative humidity (30 °C to 40 °C)
- 45% relative humidity (40 °C to 50 °C)
- Protection class: IEC 60529: IP30 (jaw closed)
- Operating altitude: 2000 m
- Storage altitude: 12000 m
- Current sensor action category: IEC 61557-13: Class 2, ≤30 A / m
Electromagnetic compatibility (EMC)
International- IEC 61326-1: Industrial Electromagnetic Environment
- CISPR 11: Group 1 Class B
- Group 1: Generated inside the equipment and / or use radio frequency energy associated with conducting the energy for the device's own internal functions is essential.
- Class B: Equipment for home appliances and residential buildings directly connected to a low voltage power supply network equipment. When this device is connected to a test object, it may exceed the emission levels produced by CISPR 11 requirements.
- Korea (KCC): A type of equipment (radio and communication equipment industry)
- Class A: This product meets the requirements of industrial electromagnetic equipment, vendors or users should be aware of this. This device is intended for use in a commercial environment, instead of the home environment.
- USA (FCC): 47 CFR 15 B Subpart. In accordance with section 15.103 provides that the products are considered tax-free device.
-