The Fluke 1577 Insulation Multimeters combine a digital insulation tester with a full-featured, true RMS digital multimeter in a single, compact, handheld unit, which provides maximum versatility for both troubleshooting and preventative maintenance.
- Insulation test voltages 500 V, 1000 V
- Insulation test: 0.1 MΩ to 600 MΩ
- Auto discharge of capacitive voltage
- AC/DC Voltage
- DC millivolts
- AC/DC milliamps
- Resistance (0.1 Ω to 50 MΩ)
- Continuity
- Three-year warranty
- Remote probe, test leads, alligator clips
- Rugged, utility hard case
- Auto power off to save battery power
- True RMS
- Large display with backlight
- Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
- CAT III 1000V, CAT IV 600V measurement category
- Accepts optional Fluke TPAKTM magnetic hanging system to free your hands for other work
Specifications:
- Voltage DC:
- Maximum voltage: 1000 V
- Accuracy: ±(0.2%+2)
- Maximum resolution: 0.001 V
- Voltage AC:
- Maximum voltage: 1000 V
- Accuracy: ±(2%+3)
- Maximum resolution: 0.1 mV
- Current DC:
- Maximum amps: 400 mA
- Amps accuracy: ±(1.0%+2)
- Maximum resolution: 0.01 mA
- Current AC:
- Maximum amps: 400 mA
- Amps accuracy: ±(2.0%+2)
- Maximum resolution: 0.01 mA
- Resistance:
- Maximum resistance: 50 MΩ
- Accuracy: ±(1.2%+2)
- maximum resolution: 0.1Ω
- Minimum test current @ 1kΩ/V: 1 mA
- Test voltages: 500, 1000 V
- Maximum resistance per test voltage:
- 50 V
- 100 V
- 250 V
- 500 V
- 1000 V: 600 MΩ
- Maximum resolution per test voltage:
- 50 V: 0.01 MΩ
- 100 V: 0.01 MΩ
- 250 V: 0.1 MΩ
- 500 V:0.1 MΩ
- 1000 V: 0.1 MΩ
- Accuracy per test voltage:
- 50 V: ±(3% + 5)
- 100 V: ±(3% + 5)
- 250 V: ±(1.5% + 5)
- 500 V: ±(2.0% + 5)
- 1000 V: ±(2.0% + 5)
- Operating temperature: –20°C to +55°C
- Storage temperature: -40°C to +60°C
- Humidity (without condensation):
- 0% - 95% (10°C – 30°C)
- 0% - 75% (30°C – 40°C)
- 0% - 40% (40°C – 55°C)
- Operating altitude: 2000 m
- Overvoltage category: Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement CAT III 1000 V and CAT IV 600 V
- Agency approvals: 2000 m CAT III 1000 V, CAT IV 600 V; 3000 m CAT II 1000 V, CAT III 600 V
- Battery life alkaline:
- Meter use: 1000 hours
- Insulation test use: Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
- IP rating: IP40
-