Home / FLUKE Insulation Multimeter FLU1577

FLUKE Insulation Multimeter FLU1577

Quantity
ADD TO CART
BUY IT NOW
  • Detail

    The Fluke 1577 Insulation Multimeters combine a digital insulation tester with a full-featured, true RMS digital multimeter in a single, compact, handheld unit, which provides maximum versatility for both troubleshooting and preventative maintenance.

    • Insulation test voltages 500 V, 1000 V
    • Insulation test: 0.1 MΩ to 600 MΩ
    • Auto discharge of capacitive voltage
    • AC/DC Voltage
    • DC millivolts
    • AC/DC milliamps
    • Resistance (0.1 Ω to 50 MΩ)
    • Continuity
    • Three-year warranty
    • Remote probe, test leads, alligator clips
    • Rugged, utility hard case
    • Auto power off to save battery power
    • True RMS
    • Large display with backlight
    • Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
    • CAT III 1000V, CAT IV 600V measurement category
    • Accepts optional Fluke TPAKTM magnetic hanging system to free your hands for other work

    Specifications:

    • Voltage DC:
      • Maximum voltage: 1000 V
      • Accuracy: ±(0.2%+2)
      • Maximum resolution: 0.001 V
    • Voltage AC:
    • Maximum voltage: 1000 V
      • Accuracy: ±(2%+3)
      • Maximum resolution: 0.1 mV
    • Current DC:
      • Maximum amps: 400 mA
      • Amps accuracy: ±(1.0%+2)
      • Maximum resolution: 0.01 mA
    • Current AC:
      • Maximum amps: 400 mA
      • Amps accuracy: ±(2.0%+2)
      • Maximum resolution: 0.01 mA
    • Resistance:
      • Maximum resistance: 50 MΩ
      • Accuracy: ±(1.2%+2)
      • maximum resolution: 0.1Ω
    • Minimum test current @ 1kΩ/V: 1 mA
    • Test voltages: 500, 1000 V
    • Maximum resistance per test voltage:
      • 50 V
      • 100 V
      • 250 V
      • 500 V
      • 1000 V: 600 MΩ
    • Maximum resolution per test voltage:
      • 50 V: 0.01 MΩ
      • 100 V: 0.01 MΩ
      • 250 V: 0.1 MΩ
      • 500 V:0.1 MΩ
      • 1000 V: 0.1 MΩ
    • Accuracy per test voltage:
      • 50 V: ±(3% + 5)
      • 100 V: ±(3% + 5)
      • 250 V: ±(1.5% + 5)
      • 500 V: ±(2.0% + 5)
      • 1000 V: ±(2.0% + 5)
    • Operating temperature: –20°C to +55°C
    • Storage temperature: -40°C to +60°C
    • Humidity (without condensation):
      • 0% - 95% (10°C – 30°C)
      • 0% - 75% (30°C – 40°C)
      • 0% - 40% (40°C – 55°C)
    • Operating altitude: 2000 m
    • Overvoltage category: Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement CAT III 1000 V and CAT IV 600 V
    • Agency approvals: 2000 m CAT III 1000 V, CAT IV 600 V; 3000 m CAT II 1000 V, CAT III 600 V
    • Battery life alkaline:
      • Meter use: 1000 hours
      • Insulation test use: Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
    • IP rating: IP40
  • Customer Reviews